Here are some common formulas that are frequently used in the field.
Options:
- Motor Formulas
- Transformer Formulas
E = Voltage / I = Amps /W = Watts / PF = Power Factor / Eff = Efficiency / HP = Horsepower
AC/DC Formulas | ||||
To Find | Direct Current | AC /
1phase 115v or 120v |
AC /
1phase 208,230, or 240v |
AC 3
phase All Voltages |
Amps when Horsepower is Known |
HP x 746 E x Eff |
HP x 746 E x Eff X PF |
HP x 746 E x Eff x PF |
HP x 746 1.73 x E x Eff x PF |
Amps when Kilowatts is known |
kW x 1000 E |
kW x 1000 E x PF |
kW x 1000 E x PF |
kW x 1000 1.73 x E x PF |
Amps when kVA is known |
kVA x 1000 E |
kVA x 1000 E |
kVA x 1000 1.73 x E |
|
Kilowatts | I x E 1000 |
I x E x PF 1000 |
I x E x PF 1000 |
I x E x 1.73 PF 1000 |
Kilovolt-Amps | I x E 1000 |
I x E 1000 |
I x E x 1.73 1000 |
|
Horsepower (output) |
I x E x Eff 746 |
I x E x Eff x PF 746 |
I x E x Eff x PF 746 |
I x E x Eff x 1.73 x PF 746 |
Three Phase Values |
For 208 volts x 1.732, use 360 For 230 volts x 1.732, use 398 For 240 volts x 1.732, use 416 For 440 volts x 1.732, use 762 For 460 volts x 1.732, use 797 For 480 Volts x 1.732, use 831 |
E = Voltage / I = Amps /W = Watts / PF = Power Factor / Eff = Efficiency / HP = Horsepower
AC Efficiency and Power Factor Formulas | ||
To Find | Single Phase | Three Phase |
Efficiency | 746 x HP E x I x PF |
746 x HP E x I x PF x 1.732 |
Power Factor | Input Watts V x A |
Input Watts E x I x 1.732 |
Power - DC Circuits |
Watts = E xI |
Amps = W / E |
Ohm's Law / Power Formulas | |
P = watts I = amps R = ohms E = Volts |
Voltage Drop Formulas | |||||
Single Phase (2 or 3 wire) |
VD = | 2 x K x I x L CM |
K = ohms per mil foot (Copper = 12.9 at 75°) (Alum = 21.2 at 75°)
L = Length of conductor in feet |
||
CM= | 2K x L x I VD |
||||
Three Phase | VD= | 1.73 x K x I x L CM |
|||
CM= | 1.73 x K x L x I VD |
Check out these Online Calculators!
If there is anything you would like to add or if you have any comments please feel free to email E.T.E. at http://www.elec-toolbox.com/email.htm.